Control sub-menu

The user can control outdoor devices through LCD screen. Control sub-menu is provided for
the operation. The user can manipulate it by pressing Operation keys. Note that Control sub-
menu is only applicable when the IED is running in "LOCAL" mode†; an error message is
shown on the LCD screen if when the IED is running in "REMOTE" mode. Remember that the
IED can change to "REMOTE" mode itself if the IED does not have local operation for a while;
then, the IED will be monitored remotely. Figure 12.11-1 shows "Control" sub-menu.
Figure 12.11-1 Control sub-menu on LCD screen
†Note: The IED is going to run in "Local" mode, when the LCD screen displays the
following menus: "Main Menu", "Control sub-menu", "Selection Executing",
"Operating completed", "Operating canceled" or "Operating failed".
Table 12.11-1 shows how to operate by the IED front panel. For more information, see
Chapter Control and monitoring application: DPOS
Table 12.11-1 Control step in DIR mode or SBO mode
Control Scheme
Direct Control
Operation Mode‡
Select Before
Control
Operation
Mode‡
‡Note: We discuss DIR and SBO modes in
mode
(→p. 361)
Control
10:48
_DPOS
Operation step
1) Set DIR mode in each control function.
2) Select a device and choose DIR, and press ENTER.
3) Press I (Close) or O
4) A signal of control command is issued; control operation is
performed.
1) Set SBO mode in each control function.
2) Select a device and choose SBO, and press ENTER.
3) Verify that the selection is performed correctly and normally.
4) Press
I (Close) or O
5) Control operation is carried out.
.
- 908 -
1/1
>
→p. 424).
(Open)
(Open); controlling command is issued.
Chapter General control function: Control