PIXIT for Reporting model (continued)
ID
Ed
What is the buffer size for each BRCB or how
many reports can be buffered
Rp7
1,2
Pre-configured
Rp8
-
dynamic, compare SCL report settings
May the reported data set contain:
- structured data objects
Rp9
1
- data attributes
What is the scan cycle for binary events
Rp10
1,2
Is this fixed, configurable
Does the device support to pre-assign a RCB to a
Rp11
1
specific client in the SCL
After restart of the server is the value of ConfRev
restored from the original configuration or
Rp12
2
retained prior to restart
Does the server accepts any client to
configure/enable a BRCB with ResvTms=‐1?
What fields are used to do the identification?
Rp13
1,2
When BRCB.ResvTms is exposed, what is
default value for BRCB.ResvTms if client does
not write (must be > 0)
Rp14
2
Or
When BRCB.ResvTms is not exposed, what is
the internal reservation time (must be >= 0)
Is it supported to change LLN0.Mod online?
10.
PIXIT FOR LOGGING MODEL
Not applicable
Description
RCB
attributes
<additional items>
- 963 -
Value / Clarification
For example, LLN0$ST$Health
can be stored 408 events.
that
are
More than 1.6 milliseconds
Configurable
Restored from original
configuration
AE‐Qualifier N
<other field> N
6F2T0200 (0.15)
(PIXIT Ed.1&Ed.2)
Deprecated
Y
Y
N
N
AP‐Title N
N/A
60 seconds
N
GRE200 (1,2)