Toshiba GR-200 Series Instruction Manual page 851

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Setting for time-tagged measurands
(iii)
For Time-tagged measurand frame in the IEC 60870-5-103 standard, event information
supplemented with numerical information are responded for Class 1 request from upper
system (station). The IED can provide event information, which is converted the numerical
information in metering table according to user setting weight, by using Time-tagged
measurand frame about the signal assigned (i.e., the Data ID).
When the "Time-tagged measurand" item is selected on the GR-TIEMS, the setting
screen is displayed.
Type ID=4 (Time-tagged measurand with relative time) can be set in this screen. In one
frame of Time-tagged measurand, the INF, FUN, Sig No., Rev, COT and SCL must be set
and the maximum eight frames of Time-tagged measurand can be set. The information
number of the frame is determined by the INF setting. The most left item "No." is only serial
number and can be skipped.
Common address is linked with the address setting† in the IED.
†For more information, see
In the transmission format of Type ID=4 (Time-tagged measurand with relative time),
customized items are shown in Table 11.5-9.
Table 11.5-9
Oct.
Item
1
Start
2
Length
3
Length
4
Start
5
Control field
6
Address
7
Type identification (Type ID)
8
Variable structure qualifier
9
Cause of transmission (COT)
10
Common address of ASDU
Figure 11.5-8 Time-tagged measurands
Appendix: IEC 60870-5-103 interoperability
Time-tagged measurand with relative time (Type ID=4)
08H+ACD+DFC
1/7/11/12
- 832 -
Value
68H
20
20
68H
1-254
Setting from the relay
4
81H
Customized by GR-TIEMS
1-254
Linked with Address setting
6F2T0200 (0.15)
(→page 989).
Remarks
GRE200 (1,2)