Toshiba GR-200 Series Instruction Manual page 453

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Signals from user-PLC logic
ON-control command requiring ILK† checking
(PLC #1 connection point)
512001 800301EE33
DEV01_CL_INTERLOCK
ILK† condition ("ON") passed
DPOS01-Close
ON-control command requiring no ILK† checking
(PLC#2 connection point)
512001 800301EE32
DEV01_CL_COMMAND
Figure 4.1-10 Select 'On' using the PLC function in DPOS01
†Note: The software interlocking (ILK) function provides the operation criteria for "On".
The ILK function is discussed separately; note that the operation criteria is
defined in the ILK function itself (i.e., the user cannot set the condition).
‡Note: A "select condition" signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.
Note: To identify the input and output points of the other DPOS logics, see Table 4.1-1
††
for the inputs (PLC#1 and PLC#2) and Table 4.1-8 for the outputs.
Select logic in DPOS01
DPOS01 function (Function ID: 512001)
For DIR operation
Operate command
with ILK† condition
For DIR operation
Operate command
without ILK† condition
PLC in DIR operate
Select condition‡
- 434 -
1≥
&
&
0
0
&
6F2T0200 (0.15)
Output
To "Wait for a next
command"
To BO connection
"DPOS01_OSL_BO_CSF"
(512001_8603011DC6)
t
Select "success"
0.1s
To "Wait for a command"
t
Select "Failed"
0.6s
††
GRE200 (1,2)