Appendix A. Specifications
Environmental and safety standards (continued)
Operating altitude
Transit altitude
Audible noise
Battery, EBM
Extended Battery Module ( EBM )
Rating
240VDC 20 x 12V, 9 Ah
Fuse
80 A
Type
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum
3-year float service life at 25 °C (77 °F).
Monitoring
Advanced monitoring for earlier failure detection and warning
Battery port
External three-pole SBS75G White connector on Power Module for connecting to
EBM
EBM battery
40 cm (15.75 in)
cable length
Communication options
Communication bay
Compatible connectivity cards UPS Network Management Card (included)
Communication ports
Relay output contacts
Remote On/Off
Remote Power Off
Hotswap MBP specifications
Input
Input bypass
Output
264
Up to 3,000 meters (9,843 ft) above sea level with 10 % derating per
1000m
Up to 10,000 meters (32,808 ft) above sea level
< 48 dBA at 1 metre typical for 6-8kVA models
< 50 dBA at 1 metre typical for 11kVA model
1 available independent communication bay for connectivity
RS-232 (DB9): 1200-19200 bps
USB: 19200 bps
4 relay outputs (normally open or normally closed)
2 pins jumper (normally open)
3 pins jumper (normally open or normally closed)
8 / 11 kVA, Single phase
Terminal blocks
n/a
4x C19 + Terminal blocks
8 / 11 kVA, Three phase
Terminal blocks
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG