Lenovo 5594-8KX User, Installation And Maintenance Manual page 116

6u rack or tower ups rt 8.0 kva and rt 11.0 kva and maintenance bypass
Hide thumbs Also See for 5594-8KX:
Table of Contents

Advertisement

Chapter 6 Power cables connection
13. Connect the MBP detection cable
14. Put back and secure the I/O terminal blocks cover of the UPS.
15. Remove the top cover
16. Punch the knockouts of MBP I/O cover
inside.
17. Insert the Normal AC source cable through the cable gland (or a conduit through the conduit
fitting).
18. Connect the wires to the Normal AC source (Input) terminal blocks of MBP.
19. Insert the Output cable through the cable gland (or a conduit through the conduit fitting).
20. Connect the wires to the Output terminal blocks of MBP.
21. Put back the MBP I/O cover
22. Put back the top cover
88
to the specific UPS connector, see
of the MBP I/O cover 1 after removing the 3 screws.
and insert cable glands of UPS (or conduit fittings)
and secure it with 4 screws on the MBP casing.
of the MBP I/O cover
and secure it with 3 screws.
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
Figure 1, item
10.

Advertisement

Table of Contents
loading

This manual is also suitable for:

5594-8px5594-9kx5594-9px

Table of Contents