Chapter 11 Troubleshooting
Alarms and faults (continued)
Condition
Batteries disconnected
End of battery life
Bypass mode
LED is on.
Power overload or Overload
or
LED is On.
Beep continuous.
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
Possible cause
The UPS does not recognize
internal battery packs.
The battery packs are not
connected.
The battery has reached end-
of-life.
An overload or a fault has
occurred, or a command has
been received to put the UPS
into Bypass mode.
Power requirements exceed
the UPS capacity (greater than
100 % of nominal; see also
Appendix A. Specifications
additional information.
Action
If the condition persists,
contact Lenovo support.
Verify that all battery packs are
connected properly.
If the condition persists,
contact Lenovo support.
The batteries must be replaced
now. Contact Lenovo support
for battery-pack replacement.
See also
Determining how
many battery packs are to
be replaced
in
additional information.
Check for one of the following
alarms: over temperature,
overload or UPS failure.
Check whether a remote
operator has issued a
command the UPS into Bypass
mode.
Remove some of the
equipment from the UPS.
for
The UPS continues to operate,
but it might switch to Bypass
mode or shut down if the load
increases.
The alarm resets when the
condition becomes inactive.
Chapter 10
for
167