Chapter 6 Power cables connection
Attention! Do not mount the MBP behind the UPS as you will not be able to attach the cables!
Connect the cables in the conduits to the terminal blocks BEFORE seating the conduits
into the collars. This will give you maximum slack in the cables and make connecting to
the terminal blocks possible. The conduits can be released from the collars by prying
out on the catch tabs on the collars and pulling the conduit.
Attention! Do not pull the cables out of the conduits. The conduit is required for safety and the
cables are difficult to get back into the conduits.
Connecting the UPS to the MBP
Attention! Detailed wiring instructions can be found in the sections
connection
A diagram displaying the hardwire connections and C19 outlets are displayed below.
Note: The Hardwire output (purple) can be used to connect Power Distribution Units (PDUs) to
provide additional outlets.
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
and
Three phase MBP power cables connection
Single phase MBP power cables
of this chapter.