Chapter 12 Helpful information
The hard wiring output from the Maintenance Bypass (MBP) can be used in addition to the
receptacles on the MBP. They both connect to the output of the UPS/Utility. That hard wiring
output can be a PDU as long as it does not exceed the rating of the UPS/Utility and would
have the proper circuit protection per local electrical codes.
It is important to not overload the UPS unit and to follow local laws and regulations with
respect to attaching a PDU to a UPS unit.
Attachment points
Figures 61 and 62 show the attachment points of the 1:1 and the 1:3 8 kVA and 11 kVA UPS
units.
224
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG