Appendix A. Specifications
Overview - 8 kVA UPS units (continued)
Specification
General
Leakage current
Energy Star compliant
Electrical input
Input voltage
Input frequency
Frequency slew rate
Max input amperage
Input connector
Input line cord
Electrical output
Output voltage settings
Output frequency
Output power capacity
Output connectors
Battery type
Battery management
Battery replacement
External battery support
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
RT8kVA 6U Rack or Tower
UPS (200-240VAC)
Leakage current of the equipment is up to 5% of input current for
the leakage current defined by the Input ground to UPS chassis
per the UL standard 60950 5.1 Touch current and protective
conductor current.
For additional information see the section
information
Chapter
in
Yes
200 - 240 V
,
AC
1-Phase
50 – 60 Hz
1 Hz / s
0.5 Hz / s HE Mode
40 A
Hardwired terminal block
Onsite wiring required
200/208/220/230/240 V
50/60 Hz
200 - 240 V
: 8000 VA/7200 W
AC
4x IEC 320-C19 (16 A) (on the MBP)
Valve Regulated Lead Acid (VRLA): Maintenance-free, sealed,
leak-proof
ABM technology or temperature-compensated charging method
(user selectable), automatic battery test and deep discharge
protection, and automatic recognition of external battery units
Hot-swap standard and extended battery modules
Up to 4 (PN 55949BX)
RT8kVA 6U 3:1 Phase Rack
or Tower UPS (380-415VAC)
Leak current
12.
No
380 - 415 V
3-Phase
50 – 60 Hz
1 Hz / s
0.5 Hz / s HE Mode
40 A
AC
,
AC
253