Lenovo 5594-8KX User, Installation And Maintenance Manual page 158

6u rack or tower ups rt 8.0 kva and rt 11.0 kva and maintenance bypass
Hide thumbs Also See for 5594-8KX:
Table of Contents

Advertisement

Chapter 10 UPS maintenance
Clearing the Battery Replacement message
When the battery replacement reminder is displayed and the batteries were replaced, perform
these steps in order to clear the reminder message:
1. In the LCD message click on OK with the Enter key
2. Move the cursor to the "No" field and click the Entery key
3. A confirmation message will be displayed that the alarm has been cleared
4. A reminder is displayed that the batteries should be replaced in this month
Note: If in step 2 "Yes" is selected, then a reminder message will be displayed after 30 days that the
battery is to be replaced. At that point replace the battery or delay for another month.
Attention! After clearing this message once it is strongly recommended to replace the UPS batteries
in order to ensure that the UPS is still able to protect the load as intended!
130
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG

Advertisement

Table of Contents
loading

This manual is also suitable for:

5594-8px5594-9kx5594-9px

Table of Contents