ABB ACS550-02 User Manual page 84

Drives 110/150...355 kw/550 hp
Hide thumbs Also See for ACS550-02:
Table of Contents

Advertisement

82
Group 11: Reference Select
This group defines:
• How the drive selects between command sources.
• Characteristics and sources for
Code Description
1101 KEYPAD REF SEL
Selects the reference controlled in local control mode.
1 =
1 (Hz/rpm) – Reference type depends on parameter 9904
REF
• Speed reference (rpm) if 9904 = 1 (
• Frequency reference (Hz) if 9904 = 3 (
2 =
2 (%)
REF
1102 EXT1/EXT2 SEL
Defines the source for selecting between the two external control locations
Start/Stop/Direction commands and reference signals.
0 =
1 – Selects external control location 1 (
EXT
• See parameter 1001
• See parameter 1103
1 =
1 – Assigns control to
DI
2...6 =
2...
6 – Assigns control to
DI
DI
7 =
2 – Selects external control location 2 (
EXT
• See parameter 1002
• See parameter 1106
8 =
– Assigns control of the drive via external control location
COMM
• Bit 5 of the Command Word 1 (parameter 0301) defines the active external control location (
• See Fieldbus user's manual for detailed instructions.
9 =
1 – Assigns control to
TIMER FUNCTION
activated =
2; Timer Function de-activated =
EXT
10...12 =
TIMER FUNCTION
Timer Function 1 above.
-1 =
1(
) – Assigns control to
DI
INV
2).
EXT
-2...-6 =
2(
)...
6(
DI
INV
DI
1(
) above.
DI
INV
1103 REF1 SELECT
Selects the signal source for external reference
0 =
– Defines the control panel as the reference
KEYPAD
source.
1 =
1 – Defines analog input 1 (
AI
source.
2 =
2 – Defines analog input 2 (
AI
source.
3 =
1/
– Defines analog input 1 (
AI
JOYST
joystick operation, as the reference source.
• The minimum input signal runs the drive at the maximum
reference in the reverse direction. Define the minimum
using parameter 1104.
• The maximum input signal runs the drive at maximum
reference in the forward direction. Define the maximum
using parameter 1105.
• Requires parameter 1003=3 (request).
Warning! Because the low end of the reference range
commands full reverse operation, do not use 0 V as the lower end of the reference range. Doing so means
that if the control signal is lost (which is a 0 V input) the result is full reverse operation. Instead, use the
following set-up so that loss of the analog input triggers a fault, stopping the drive:
• Set parameter 1301
• Set parameter 3021
• Set parameter 3001
4 =
2/
– Defines analog input 2 (
AI
JOYST
• See above (
2/
AI
JOYST
Start-Up
:
VECTOR
SPEED
SCALAR
EXT
1
for
1's Start/Stop/Dir definitions.
EXT
COMMANDS
EXT
1
for
1's reference definitions.
SELECT
EXT
REF
1 or
2 based on the state of
EXT
EXT
1 or
2 based on the state of the selected digital input. See
EXT
EXT
EXT
2
for
2's Start/Stop/Dir definitions.
EXT
COMMANDS
EXT
2
for
2's reference definitions.
SELECT
EXT
REF
1 or
EXT
2... 4 – Assigns control to
1 or
2 based on the state of
EXT
EXT
) – Assigns control to
INV
EXT
REF
1) as the reference
AI
2) as the reference
AI
1), configured for
AI
1 (1304
MINIMUM AI
MINIMUM AI
1
to a value 5% or higher.
AI
FAULT LIMIT
<
to 1 (
AI
MIN FUNCTION
FAULT
2), configured for joystick operation, as the reference source.
AI
) description.
1 and
2.
REF
REF
MOTOR CTRL MODE
) or 2 (
:
).
VECTOR
TORQ
:
).
SPEED
EXT
1).
1 (
1 activated =
DI
DI
2).
1 or
EXT
EXT
2 based on the state of the Timer Function (Timer Function
EXT
1). See Group 36, Timer Functions.
EXT
1 or
2 based on the state of the Timer Function. See
EXT
EXT
1 (
1 activated =
DI
DI
1 or
2 based on the state of the selected digital input. See
EXT
1
EXT REF
MAX
1.
1
EXT REF
MIN
-
1
EXT REF
MIN
-
1
EXT REF
MAX
2 V / 4 mA
0 V / 0 mA
Hysteresis 4 % of Full Scale
2) at 20% (2 V or 4 mA).
).
.
1 or
2. Thus, defines the source for
EXT
2;
1 de-activated =
EXT
DI
1 above.
DI
2 based on the fieldbus control word.
1 or
EXT
EXT
1;
1 de-activated =
EXT
DI
1
EXT REF
MIN
-2 %
-
1
EXT REF
MIN
1).
EXT
2).
10 V /
20 mA
+2 %

Advertisement