138
Code Description
8104 REFERENCE STEP 2
Sets a percentage value that is added to the process reference.
• Applies only when at least two auxiliary (constant speed) motors are running.
• See parameter 8103
8105 REFERENCE STEP 3
Sets a percentage value that is added to the process reference.
• Applies only when at least three auxiliary (constant speed) motors are running.
• See parameter 8103
8109 START FREQ 1
Sets the frequency limit used to start the first auxiliary motor. The first auxiliary motor starts if:
• No auxiliary motors are running.
• ACS550 output frequency exceeds the limit:
8109 + 1 Hz.
• Output frequency stays above a relaxed limit
(8109 - 1 Hz) for at least the time: 8115
After the first auxiliary motor starts:
• Output frequency decreases by the value =
(8109
START FREQ
• In effect, the output of the speed regulated motor drops to
compensate for the input from the auxiliary motor.
See figure, where:
• A = (8109
START FREQ
• B = Output frequency increase during the start delay.
• C = Diagram showing auxiliary motor's run status as frequency
increases (1 = On).
Note! 8109
START FREQ
• 8112
1
LOW FREQ
• (2008
MAXIMUM FREQ
8110 START FREQ 2
Sets the frequency limit used to start the second auxiliary motor.
• See 8109
START FREQ
The second auxiliary motor starts if:
• One auxiliary motor is running.
• ACS550 output frequency exceeds the limit: 8110 + 1.
• Output frequency stays above the relaxed limit (8110 - 1 Hz) for at least the time: 8115
8111 START FREQ 3
Sets the frequency limit used to start the third auxiliary motor.
• See 8109
START FREQ
The third auxiliary motor starts if:
• Two auxiliary motors are running.
• ACS550 output frequency exceeds the limit: 8111 + 1 Hz.
• Output frequency stays above the relaxed limit (8111 - 1 Hz) for at least the time: 8115
Start-Up
1.
REFERENCE STEP
1.
REFERENCE STEP
AUX MOT START D
1) - (8112
1).
LOW FREQ
1) - (8112
1)
LOW FREQ
1 value must be between:
) -1.
1 for a complete description of the operation.
1 for a complete description of the operation.
f (Hz)
f
MAX
.
(P 8109)+1
P 8109
A
P 8112
f
MIN
C
1
0
P 8115
B
A
.
AUX MOT START D
.
AUX MOT START D
t
t