ABB ACS550-02 User Manual page 162

Drives 110/150...355 kw/550 hp
Hide thumbs Also See for ACS550-02:
Table of Contents

Advertisement

160
Bit
12
13... 15
Note! Operation of
Profile with one exception:
ACS550.
Example. Using the
• First, the requirements for using the
• When the power is first connected, the state of the drive is not ready to switch on.
See dotted lined path (
• Use the
OPERATING
given reference. See table below.
Step
1
2
3
4
5
6
Start-Up
Value
Description (Correspond to states/boxes in the state diagram)
1
Run Enable signal received
0
No Run Enable signal received
Unused
CONTROL WORD
CONTROL WORD
CONTROL WORD
to step through the state machine states until the
CONTROL WORD
state is reached, meaning that the drive is running and follows the
CONTROL WORD Value
CW = 0000 0000 0000 0110
bit 15
bit 0
CW = 0000 0000 0000 0111
CW = 0000 0000 0000 1111
CW = 0000 0000 0010 1111
CW = 0000 0000 0110 1111
40004
STATUS WORD
and
STATUS WORD
bit 10 (
REMOTE
to start the drive:
CONTROL WORD
) in the state diagram below.
This CW value changes the drive state to
.
ON
Wait at least 100 ms before proceeding.
This CW value changes the drive state to
This CW value changes the drive state to
The drive starts, but will not accelerate.
This CW value releases the ramp function generator (RFG)
output, and changes the drive state to
.
ENABLED
This CW value releases the ramp function generator (RFG)
output, and changes the drive state to
accelerates to the given reference and follows the reference.
conform to the ABB Drives
_
) is not used by the
CMD
must be met. See above.
Description
READY TO SWITCH
READY TO OPERATE
OPERATION ENABLED
:
RFG
ACCELERATOR
. The drive
OPERATING
.
.