ABB ACS550-02 User Manual page 110

Drives 110/150...355 kw/550 hp
Hide thumbs Also See for ACS550-02:
Table of Contents

Advertisement

108
Group 30: Fault Functions
This group defines situations that the drive should recognize as potential faults and
defines how the drive should respond if the fault is detected.
Code Description
3001 AI<MIN FUNCTION
Defines the drive response if the analog input (
chain).
• 3021
1
AI
FAULT LIMIT
0 =
– No response.
NOT SEL
1 =
– Displays a fault (7,
FAULT
2 =
7 – Displays a warning (2006,
CONST SP
3 =
– Displays a warning (2006,
LAST SPEED
This value is the average speed over the last 10 seconds.
Warning! If you select
input signal is lost.
3002 PANEL COMM ERR
Defines the drive response to a control panel communication error.
1 =
– Displays a fault (10,
FAULT
2 =
7 – Displays a warning (2008,
CONST SP
3 =
– Displays a warning (2008,
LAST SPEED
the average speed over the last 10 seconds.
Warning! If you select
panel communication is lost.
3003 EXTERNAL FAULT 1
Defines the External Fault 1 signal input and the drive response to an external fault.
0 =
– External fault signal is not used.
NOT SEL
1 =
1 – Defines digital input
DI
• Activating the digital input indicates a fault. The drive displays a fault (14,
stop.
2...6 =
2...
6 – Defines digital input
DI
DI
• See
1 above.
DI
-1 =
1(
) – Defines an inverted digital input
DI
INV
• De-activating the digital input indicates a fault. The drive displays a fault (14,
stop.
-2...-6 =
2(
)...
6(
DI
INV
DI
• See
1(
) above.
DI
INV
3004 EXTERNAL FAULT 2
Defines the External Fault 2 signal input and the drive response to an external fault.
• See parameter 3003 above.
3005 MOT THERM PROT
Defines the drive response to motor overheating.
0 =
– No response and/or motor thermal protection not set up.
NOT SEL
1 =
– When the calculated motor temperature exceeds 90 C, displays a warning (2010,
FAULT
the calculated motor temperature exceeds 110 C, displays a fault (9,
2 =
– When the calculated motor temperature exceeds 90 C, displays a warning (2010,
WARNING
3006 MOT THERM TIME
Sets the motor thermal time constant for the motor temperature
model.
• This is the time required for the motor to reach 63% of the final
temperature with steady load.
• For thermal protection according to UL requirements for NEMA
class motors, use the rule of thumb:
35 times t6, where t6 (in seconds) is specified by the motor
manufacturer as the time that the motor can safely operate at six
times its rated current.
• The thermal time for a Class 10 trip curve is 350 s, for a Class
20 trip curve 700 s, and for a Class 30 trip curve 1050 s.
Start-Up
) signal drops below the fault limits and
AI
and 3022
2
set the minimum limits
AI
FAULT LIMIT
1
or 8,
2
AI
LOSS
AI
1
AI
LOSS
1
AI
LOSS
7 or
CONST SP
LAST SPEED
) and the drive coasts to stop.
PANEL LOSS
PANEL LOSS
PANEL LOSS
7 or
CONST SP
LAST SPEED
1 as the external fault input.
DI
2...
6 as the external fault input.
DI
DI
1 as the external fault input.
DI
) – Defines an inverted digital input
INV
MOTOR THERM TIME
) and the drive coasts to stop.
LOSS
or 2007,
2
) and sets speed using 1208
AI
LOSS
or 2007,
2
) and sets speed using the last operating level.
AI
LOSS
, make sure that continued operation is safe when the analog
) and sets speed using 1208
) and sets speed using the last operating level. This value is
, make sure that continued operation is safe when the control
2...
6 as the external fault input.
DI
DI
MOT OVERTEMP
Motor load
Temp. Rise
100%
equals
63%
is used in reference
AI
CONST SPEED
7.
CONST SPEED
1) and the drive coasts to
EXT FAULT
1) and the drive coasts to
EXT FAULT
MOT OVERTEMP
) and the drive coasts to stop.
MOT OVERTEMP
P 3006
7.
). When
).
t
t

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs550-u2Acs550-01Acs550-u1

Table of Contents