Code Description
8117 NR OF AUX MOT
Sets the number of auxiliary motors.
• Each auxiliary motor requires a relay output, which the drive uses to send start/stop signals.
• The Autochange function, if used, requires an additional relay output for the speed regulated motor.
• The following describes the set-up of the required relay outputs.
Relay Outputs
As noted above, each auxiliary motor requires a relay output, which the drive uses to send start/stop signals. The
following describes how the drive keeps track of motors and relays.
• The ACS550 provides relay outputs RO1...RO3.
• An external digital output module can be added to provide relay outputs RO4...RO6.
• Parameters 1401...1403 and 1410...1412 define, respectively, how relays RO1...RO6 are used – the parameter
value 31
defines the relay as used for PFC.
PFC
• The ACS550 assigns auxiliary motors to relays in ascending order. If the Autochange function is disabled, the first
auxiliary motor is the one connected to the first relay with a parameter setting = 31
Autochange function is used, the assignments rotate. Initially, the speed regulated motor is the one connected to
the first relay with a parameter setting = 31
with a parameter setting = 31
ACS550
Standard PFC mode
Start-Up
, the first auxiliary motor is the one connected to the second relay
PFC
, and so on.
PFC
ACS550
, and so on. If the
PFC
Relay Logic
PFC with Autochange mode