• dL P (Download Partial) – Copies a partial parameter set from the Control Panel
to a drive. The partial set does not include internal motor parameters, parameters
9905...9909, 1605, 1607, 5201, nor any Group 51 parameters. Use this option to
transfer parameters to systems that use similar configurations – the drive and
motor sizes do not need to be the same.
1. Starting from the Output mode, press MENU/ENTER.
The display shows one of the following alternate modes:
• reF (Reference)
• PAr (Parameter)
• CoPY (Copy)
2. Use UP or DOWN arrow key to step through to the "CoPY" (Copy) Mode.
3. Press MENU/ENTER.
The display shows one of the following copy options:
• uL (Upload)
• rE A (Restore All)
• dL P (Download Partial)
4. Use UP or DOWN arrow key to step to the desired option.
5. Press MENU/ENTER.
The parameter set is transferred as directed. During the transfer, the display shows
the transfer status as a percent of completion.
6. Press EXIT/RESET to step back to the Output mode.
Alarm Codes (Basic Control Panel)
The Basic Control Panel indicates Control Panel alarms with a code, A3xxx. The
following table lists the alarm codes and descriptions.
Note! Fault/Alarm codes not specific to the Basic Control Panel are defined in the
Diagnostics
Code
3001
3002
3003
3010
3011
3012
3013
3014
Start-Up
section starting on page
Communication fault.
Control Panel to Drive interface error. Call local ABB sales representative
and report the error code number.
Control Panel and drive are not both in the ACS550 family.
Parameter backup CRC failure.
Drive is controlled from another source.
Rotation direction is locked.
Key is disabled, start is inhibited.
Key is disabled, due to drive fault. Correct fault.