3.6.4 Fire Extinguishing System (Standard)

● Semi-annual maintenance of the fire extinguishing system involves system
commissioning. Before the maintenance, inform the related administrative
departments that the fire extinguishing system will be maintained and stop
working.
● Before the maintenance, disconnect all cables to fire cylinder electromagnetic
valves to avoid extinguishant release and damage to equipment due to
misoperations.
● After the maintenance, reconnect the cables to fire cylinder electromagnetic
valves and inform the administrative departments that the fire extinguishing
system has resumed.
Issue 04 (2021-02-10)
Check Standard
Off: The power supply is abnormal.
Blinking slowly: The software runs
properly (the indicator blinks at 0.5
Hz, on for 1s and then off for 1s) or
registration with the ECC800 is
successful.
Blinking at short intervals: The
communication is interrupted or the
registration with the ECC800 fails (the
indicator blinks at 4 Hz, on for 0.125s
and then off for 0.125s).
Blinking: The indicator blinks at super
short intervals for 0.5s (blinking at 10
Hz, on for 0.05s and then off for
0.05s) and then turns off for 0.5s. The
cycle lasts for 10s.
Steady on: A fault alarm is raised.
Off: No fault alarm is raised.
An alarm is raised on the ECC800
WebUI.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
If the RUN indicator is
off, check the power
supply.
If the RUN indicator
blinks at short intervals,
check whether the
communications cable
is loose or
disconnected. If so,
reconnect the cable.
Clear the alarm by
referring to the ECC800
documents.
If no alarm is raised,
replace the water
sensor.
34