Huawei FusionModule1000A40 Maintenance Manual page 33

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One
Data Center
Maintenance Guide
Check Item
Operation
RF_Z indicator
AC actuator
Power input
Power output
PWR indicator
ALM indicator
Issue 04 (2021-02-10)
Check Standard
On: No network
parameters exist. A
network is waiting to
be created.
Blinking slowly: A
network is set up, and
node access is not
allowed (the indicator
blinks at 0.5 Hz, on
for 1s and then off for
1s).
Blinking at super
short intervals: A
network is set up, and
node access is
allowed (the indicator
blinks at 10 Hz, on for
0.05s and then off for
0.05s).
Blinking at super
short intervals
intermittently: The
device is searching for
a network (the
indicator blinks at 2
Hz, on for 0.5s and
then off for 0.5s).
Input voltage: 90–240
V AC
Output voltage: 90–
240 V AC
Steady on: The power
supply is normal.
Off: No power supply
is available.
Steady on: A fault
alarm is raised.
Off: No fault alarm is
raised.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
For details, see the ECC800 documents.
Check the input power cables if the
input voltage is abnormal.
For details, contact Huawei technical
support.
Check the input power cables.
Clear the alarm by referring to the
ECC800 documents.