FusionModule1000A40 Prefabricated All-in-One
Data Center
Maintenance Guide
Alarm
Alarm
Indicator
Type
Name
2nd Stage
Isolatio
Contact
n alarm
Extract Fan
Isolatio
n alarm
Extinguisha
Startup
nt Released
alarm
Release
Startup
Imminent
alarm
1st Stage
Startup
Activated
alarm
Hold
Startup
Activated
alarm
Flooding
Fault
Zone
alarm
Low
Action
Pressure
alarm
Issue 04 (2021-02-10)
Alarm
System Action
Severity
Major
The S2 port has 24
V DC voltage
output.
Major
The Extract Fan
port has 24 V DC
voltage output.
Major
Extinguishant
release countdown
starts.
Major
Extinguishant
release starts.
Major
The alarm signal of
the first stage is
output.
Major
Countdown stops.
Major
NO and C on the
FAULT RELAY port
become closed,
while NC and C
become open.
Major
N/A
Copyright © Huawei Technologies Co., Ltd.
4 Common Faults and Troubleshooting Measures
Possible
Causes
2nd Stage
Contact is in
isolation mode.
Extract Fan is
in isolation
mode.
Extinguishant
Released has
started.
Release
Imminent has
started.
1st Stage
Activated has
started.
The stop
button has
been pressed.
1. The external
connected
repeater or
linkage
output
board does
not have
signals.
2. The S3,
Comms,
Exting,
Hold,
Manual
release,
Mode,
Release, or
Low press
fault may
exist.
Low Pressure
has started.
Solution
To clear the alarm,
press the W/DOG
RESET or PROC
RESET button.
After the component
is reset, press the
RESET button.
Check relevant cable
connections and the
external connected
repeater or linkage
output board.
Check the pressure
of the cylinder. If the
pressure is too low,
increase the pressure
or add extinguishant
in time.
45