Power Supply And Distribution System; Cooling System - Huawei FusionModule1000A40 Maintenance Manual

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One
Data Center
Maintenance Guide

3.4.1 Power Supply and Distribution System

Table 3-3 Monthly maintenance checklist for the power supply and distribution system
Item
Method
Integrate
Operating
d UPS
environment
Power grid
environment
Information on
the LCD

3.4.2 Cooling System

Table 3-4 Monthly maintenance checklist for the cooling system
Item
Method
Thermal
Check whether
insulation foam
the thermal
for the
insulation layers
humidifier/
are in good
condensate
condition without
drainpipe
condensation.
Issue 04 (2021-02-10)
Check Standard
● Ambient
temperature: 0–40°C
● Humidity: 5%–95%
RH (non-
condensing)
● Rodent-proof
measures have been
taken for the
equipment room.
● The equipment room
is airtight.
● Input voltage: 380 V
AC, 400 V AC, or 415
V AC (line voltage)
● Output voltage: 380
V AC, 400 V AC, or
415 V AC (tolerance
± 1%, line voltage)
● Frequency: 40–70 Hz
The status icons on the
LCD indicate that all
units are operating
properly, all operating
parameters are within
their normal ranges,
and no fault or alarm
information is
displayed.
Check Standard
The thermal
insulation layers
are in good
condition and
free from
condensation.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
● If the humidity or temperature is
abnormal, check the smart cooling
product status.
● Put rodent-proof baffle plates at the
door of the UPS equipment room.
● Check that the equipment room is
airtight and not in a direct
ventilation environment.
● If the input voltage is abnormal,
check the power grid status and
input cable connection.
● If the output voltage is abnormal,
check the UPS running status and
check whether an alarm is
generated.
If an alarm is generated, rectify the
fault by checking the device status and
parameters.
Troubleshooting
If there is condensation under a pipe,
replace the thermal insulation foam by
following instructions in the
NetCol5000-A025 In-row Air Cooled
Smart Cooling Product User Manual
(300 mm Width).
16