Monthly Maintenance; Power Supply And Distribution System - Huawei FusionModule1000A20 Maintenance Manual

Ct solution
Hide thumbs Also See for FusionModule1000A20:
Table of Contents

Advertisement

FusionModule1000A20 CT Solution
Maintenance Guide
Categ
ory
Fire
extingu
ishing
system

3.4 Monthly Maintenance

3.4.1 Power Supply and Distribution System

Table 3-3 Monthly maintenance checklist for the power supply and distribution system
Maintena
nce Item
PDC
Issue 01 (2019-02-25)
Mainten
Operation
ance
Item
Camera
On the ECC800
images
WebUI, choose
and
System
coverage
Settings > Video
Settings > Video
Information in
the monitoring
system, and you
can click Access
Link on the page
to access the
video link.
VESDA
Check the
and its
working status of
power
the VESDA and
supply
its power supply.
Operation
Check the
luminance of the
indicators.
Check the SPD
indicator and SPD
circuit breaker
status.
Copyright © Huawei Technologies Co., Ltd.
Check
Standard
The video
images are
properly
displayed.
The coverage of
the camera is
optimal.
The VESDA
and its power
supply are
normal.
Check
Troubleshooting
Standard
The
If the indicator is off or dim, replace
three-phase
it by following instructions in
power
5.1.2.5 Replacing an Indicator.
indicators are
steady on.
The SPD
If the SPD indicator is red, replace
indicator is
the SPD. For details, refer to 5.1.2.4
green.
Replacing an SPD.
The SPD
Switch on the circuit breaker.
circuit breaker
is switched to
ON.
3 Routine Maintenance
Troubleshooting
If no video image is
displayed:
1. Connect the camera
cable again.
2. If the cable is correctly
connected, replace the
camera by following
instructions in 5.3.5
Replacing a Camera.
If the camera coverage does
not meet the monitoring
requirement, adjust the
camera coverage.
If the VESDA or its power
supply is abnormal,
troubleshoot by following
instructions in documents
delivered with the VESDA.
18