XX:E FW

Cause
Firmware module contained in internal memory is
defective, therefore clearing of loader is impossible

XX:E LD

Cause
Firmware module contained in internal memory is
defective, therefore clearing of loader is impossible

XX:E SEQ

Cause
Command order was not complied with when drive
firmware was programmed
You tried to write to a range with valid checksum
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Handling, Diagnostic and Service Functions
Brief Description: Warning: no valid firmware available
Remedy
Carry out firmware update (by means of "Dolfi" program
or by starting command P-0-4072, C2900 Command
Firmware update from MMC)
Note:
"FL:E FW" means firmware loader and "LD:E FW" means
loader in control section.
Brief Description: Warning: no valid loader available
Remedy
Carry out firmware update (by means of "Dolfi" program
or by starting command P-0-4072, C2900 Command
Firmware update from MMC)
ATTENTION: If "Dolfi" is used for carrying out firmware
update, it is first necessary to program loader before
firmware module can be programmed
Note:
"FL:E LD" means firmware loader and "LD:E LD" means
loader in control section.
Brief Description: Warning: sequence error
Remedy
Use auxiliary program "Dolfi" or command P-0-4072,
C2900 Command Firmware update from MMC for
firmware update
– or –
Carry out shutdown before clearing or programming
drive firmware
Before writing, clear range to which data are to be
written
Note:
"FL:E SEQ" means firmware loader and "LD:E SEQ" means
loader in control section.