C2905 Programmed Firmware Defective - Bosch Rexroth IndraDrive Troubleshooting Manual

Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents

Advertisement

9-110
Command Diagnostic Messages

C2905 Programmed firmware defective

Cause
Firmware transfer from MMC was incorrect
Firmware available on MMC is not correct
An error was detected during check of flash
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Supported by Firmware Variant:
During the execution of the P-0-4072, C2900 Command Firmware
update from MMC an error occurred.
Remedy
Execute P-0-4072, C2900 Command Firmware update
from MMC again
Use a different MMC with the desired firmware
Execute P-0-4072, C2900 Command Firmware update
from MMC again.
If error occurs repeatedly, replace control section or
entire drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
Note:
If the command error occurs during the transmission of the
firmware to an optional module, the respective system error
(F8xxx) is displayed in addition to the command error C2905.
C2905 - Attributes
Display:
C2905
Mess. no.:
C2905 (hex)
Rexroth IndraDrive
FWA-INDRV*-MPH02VRS-MS
FWA-INDRV*-MPB02VRS-MS
FWA-INDRV*-MPD02VRS-MS
DOK-INDRV*-GEN-**VRS**-WA01-EN-P