External Selection Of Auto-Reclose Mode - ABB Relion 670 Series Applications Manual

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 358-UUS A
Table 27:
MODEINT (integer)
A start of a new reclosing cycle is blocked during the set "reset time" after the selected number of
reclosing shots have been made.
13.2.2.14

External selection of auto-reclose mode

The auto-reclose mode can be selected by use of the available logic function blocks. Below is an
example where the choice of mode is done from a hardware function key in front of the IED with
only 3 phase or 1/3 phase mode, but alternatively there can for example, be a physical selector
switch on the front of the panel which is connected to a binary to integer function block
(BTIGAPC).
The connection example for selection of the auto-reclose mode is shown in Figure.
INTONE
3
1/3
ANSI09000168 V1 EN-US
Figure 111: Selection of the auto-reclose mode from a hardware functional key in front of the
Application manual
Type of reclosing shots at different settings of ARMode or integer inputs to MODEINT
ARMode
1
3ph
2
1/2/3ph
3
1/2ph
4
1ph + 1*2ph
5
1/2ph + 1*3ph
6
1ph + 1*2/3ph
SLGGIO
PSTO
NAME1
NAME2
IED
Type of fault
1ph
2ph
3ph
1ph
2ph
3ph
1ph
2ph
3ph
1ph
2ph
3ph
1ph
2ph
3ph
1ph
2ph
3ph
SMBRREC (79)
SWPOSN
MODEINT
1st shot
2nd-5th shot
3ph
3ph
3ph
3ph
3ph
3ph
1ph
3ph
2ph
3ph
3ph
3ph
1ph
3ph
2ph
3ph
.....
.....
1ph
3ph
2ph
.....
.....
.....
1ph
3ph
2ph
3ph
3ph
.....
1ph
3ph
2ph
.....
3ph
.....
ANSI09000168_1_en.vsd