Loss Of Voltage Check Lovptuv (27); Identification - ABB Relion 670 Series Applications Manual

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 358-UUS A
different voltage level but the difference can also e.g. be used by voltage drop in the secondary
circuits. The setting is normally done at site by evaluating the differential voltage achieved as a
service value for each phase. The factor is defined as V2 ·
Each phase has its own ratio factor.
VDTrip : The voltage differential level required for tripping is set with this parameter. For
application on capacitor banks the setting will depend of the capacitor bank voltage and the
number of elements per phase in series and parallel. Capacitor banks must be tripped before
excessive voltage occurs on the healthy capacitor elements. The setting values required are
normally given by the capacitor bank supplier. For other applications it has to be decided case by
case. For fuse supervision normally only the alarm level is used.
tTrip : The time delay for tripping is set by this parameter. Normally, the delay does not need to be
so short in capacitor bank applications as there is no fault requiring urgent tripping.
tReset : The time delay for reset of tripping level element is set by this parameter. Normally, it can
be set to a short delay as faults are permanent when they occur.
For the advanced users following parameters are also available for setting. Default values are here
expected to be acceptable.
V1Low : The setting of the undervoltage level for the first voltage input is decided by this
parameter. The proposed default setting is 70%.
V2Low : The setting of the undervoltage level for the second voltage input is decided by this
parameter. The proposed default setting is 70%.
tBlock : The time delay for blocking of the function at detected undervoltages is set by this
parameter.
VDAlarm : The voltage differential level required for alarm is set with this parameter. For
application on capacitor banks the setting will depend of the capacitor bank voltage and the
number of elements per phase in series and parallel. Normally values required are given by
capacitor bank supplier.
For fuse supervision normally only this alarm level is used and a suitable voltage level is 3-5% if the
ratio correction factor has been properly evaluated during commissioning.
For other applications it has to be decided case by case.
tAlarm : The time delay for alarm is set by this parameter. Normally, few seconds delay can be used
on capacitor banks alarm. For fuse failure supervision (SDDRFUF) the alarm delay can be set to
zero.
8.5

Loss of voltage check LOVPTUV (27)

8.5.1

Identification

Function description
Loss of voltage check
Application manual
RFLx and shall be equal to the V1 voltage.
IEC 61850
IEC 60617
identification
identification
LOVPTUV
-
Voltage protection
ANSI/IEEE C37.2
device number
27
Section 8
SEMOD171868-1 v2
SEMOD171954-2 v2
215