Four Step Phase Overcurrent Protection Oc4Ptoc(51/67) - ABB Relion 670 Series Applications Manual

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 358-UUS A
~
ANSI09000025 V2 EN-US
Figure 54: Two parallel lines. Influence from parallel line to the through fault current: I
The minimum theoretical current setting for the overcurrent protection function (Imin) will be:
³
Imin
MAX I
EQUATION82 V1 EN-US
Where I
fA
mentioned previously, the minimum setting (Is) for the instantaneous phase overcurrent
protection 3-phase output is then:
Is ³1.3·Imin
EQUATION83 V2 EN-US
The protection function can be used for the specific application only if this setting value is equal
or less than the maximum phase fault current that the IED has to clear.
The IED setting value
value for
=
Pickup
ANSIEQUATION1147 V1 EN-US
7.2
Four step phase overcurrent protection
OC4PTOC(51/67)
Application manual
A
C
Z
A
Fault
I
IED
,
,
(
I
I
)
fA
fB
M
and I
have been described in the previous paragraph. Considering the safety margins
fB
Pickup is given in percentage of the primary base current value, IBase . The
Pickup is given from this formula:
Is
×
100
IBase
Line 1
B
Z
L1
Z
B
M
Z
L2
M
Line 2
~
ANSI09000025_2_en.vsd
Section 7
Current protection
M
(Equation 25)
(Equation 26)
(Equation 27)
SEMOD129998-1 v7
123

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents