Section 13
Control
13.4.9

Interlocking for breaker-and-a-half diameter BH (3)

13.4.9.1

Application

The interlocking for breaker-and-a-half diameter (BH_CONN(3), BH_LINE_A(3), BH_LINE_B(3))
functions are used for lines connected to a breaker-and-a-half diameter according to figure 162.
BH_LINE_A
ANSI04000513 V1 EN-US
Figure 162: Switchyard layout breaker-and-a-half
Three types of interlocking modules per diameter are defined. BH_LINE_A (3) and BH_LINE_B (3)
are the connections from a line to a busbar. BH_CONN (3) is the connection between the two lines
of the diameter in the breaker-and-a-half switchyard layout.
For a breaker-and-a-half arrangement, the modules BH_LINE_A, BH_CONN and BH_LINE_B must be
used.
13.4.9.2

Configuration setting

For application without 989 and 989G, just set the appropriate inputs to open state and disregard
the outputs. In the functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
989_OP = 1
989_CL = 0
332
189
189G
152
289G
689
389G
6189
152
989
189G
989G
BH_CONN
289
189G
152
289G
689
389G
6289
989
289G
989G
1MRK 511 358-UUS A
WA1 (A)
WA2 (B)
BH_LINE_B
en04000513_ansi.vsd
Application manual
IP14173-1 v3
M13570-3 v6
M13570-7 v4
M13569-4 v4
M13569-6 v5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents