Section 15
Logic
RefSource = 0
Set the
SetValue shall be set between -2000000000 to 2000000000.
15.14
Comparator for real inputs - REALCOMP
15.14.1
Identification
Function description
Comparator for real inputs
15.14.2
Application
The function gives the possibility to monitor the level of real values in the system relative to each
other or to a fixed value. It is a basic arithmetic function that can be used for monitoring,
supervision, interlocking and other logics.
15.14.3
Setting guidelines
Setting procedure on the IED:
EnaAbs : This setting is used to select the comparison type between signed and absolute values.
Absolute : The function will do absolute comparison between input and reference value.
Signed : The function will do signed comparison between input and reference value.
RefSource : This setting is used to select the reference source between input and setting for
comparison.
REF : The function will take reference value from input REF
SetValue : The function will take reference value from setting SetValue
SetValue : This setting is used to set the reference value for comparison when setting RefSource is
selected as
will never pickups.
RefPrefix : This setting is used to set the unit of the reference value for comparison when setting
RefSource is selected as SetValue . It has 5 unit selections and they are Milli, Unity, Kilo, Mega and
Giga.
EqualBandHigh : This setting is used to set the equal condition high band limit in % of reference
value. This high band limit will act as reset limit for INHIGH output when INHIGH is high in last
execution.
EqualBandLow : This setting is used to set the equal condition low band limit in % of reference
value. This low band limit will act as reset limit for INLOW output when INLOW is high in last
execution.
414
IEC 61850
identification
REALCOMP
SetValue . If this setting value is less than 0.2% of the set unit then the output INLOW
IEC 60617
ANSI/IEEE C37.2
identification
device number
Real<=>
GUID-DE69FF5B-7D34-4A30-9060-214E98BFF798 v1
1MRK 511 358-UUS A
GUID-0D68E846-5A15-4C2C-91A2-F81A74034E81 v1
GUID-5F7B1683-9799-4D27-B333-B184F8861A5B v1
Application manual