Setting Guidelines - ABB Relion 670 Series Applications Manual

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 358-UUS A
ANSI12000143 V1 EN-US
Figure 100: Application of VDSPVC
12.3.3

Setting guidelines

The parameters for Fuse failure supervision VDSPVC are set via the local HMI or PCM600.
The voltage input type (phase-to-phase or phase-to-neutral) is selected using
ConTypePilot parameters, for main and pilot fuse groups respectively.
The settings
VBase . Set VBase to the primary rated phase-to-phase voltage of the potential voltage
transformer.
group, that is used by VDSPVC (60), is set by the setting parameter
Application manual
The connection type for the main and the pilot fuse groups must be consistent.
Vdif Main block , Vdif Pilot alarm and VSealIn are in percentage of the base voltage,
VBase is available in the Global Base Value groups; the particular Global Base Value
A
B
C
Main Vt circuit
IED
FuseFailSupvn
ANSI12000143-1-en.vsd
Secondary system supervision
GUID-0D5A517C-1F92-46B9-AC2D-F41ED4E7C39E v1
GUID-52BF4E8E-0B0C-4F75-99C4-0BCB22CDD166 v2
GUID-0B298162-C939-47E4-A89B-7E6BD7BEBB2C v2
ConTypeMain and
GlobalBaseSel .
Section 12
251