Switches (Sxcbr/Sxswi); Reservation Function (Qcrsv And Resin) - ABB Relion 670 Series Applications Manual

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 13
Control
At error the command sequence is cancelled.
In the case when there are three one-phase switches (SXCBR) connected to the switch controller
function, the switch controller will "merge" the position of the three switches to the resulting
three-phase position. In case of a pole discrepancy situation, that is, the positions of the one-
phase switches are not equal for a time longer than a settable time; an error signal will be given.
The switch controller is not dependent on the type of switching device SXCBR or SXSWI. The
switch controller represents the content of the SCSWI logical node (according to IEC 61850) with
mandatory functionality.
13.3.1.3

Switches (SXCBR/SXSWI)

Switches are functions used to close and interrupt an ac power circuit under normal conditions, or
to interrupt the circuit under fault, or emergency conditions. The intention with these functions is
to represent the lowest level of a power-switching device with or without short circuit breaking
capability, for example, circuit breakers, disconnectors, grounding switches etc.
The purpose of these functions is to provide the actual status of positions and to perform the
control operations, that is, pass all the commands to the primary apparatus via output boards and
to supervise the switching operation and position.
Switches have the following functionalities:
Local/Remote switch intended for the switchyard
Block/deblock for open/close command respectively
Update block/deblock of position indication
Substitution of position indication
Supervision timer that the primary device starts moving after a command
Supervision of allowed time for intermediate position
Definition of pulse duration for open/close command respectively
The realizations of these function are done with SXCBR representing a circuit breaker and with
SXSWI representing a circuit switch that is, a disconnector or an grounding switch.
Circuit breaker (SXCBR) can be realized either as three one-phase switches or as one three-phase
switch.
The content of this function is represented by the IEC 61850 definitions for the logical nodes
Circuit breaker (SXCBR) and Circuit switch (SXSWI) with mandatory functionality.
13.3.1.4

Reservation function (QCRSV and RESIN)

The purpose of the reservation function is primarily to transfer interlocking information between
IEDs in a safe way and to prevent double operation in a bay, switchyard part, or complete
substation.
For interlocking evaluation in a substation, the position information from switching devices, such
as circuit breakers, disconnectors and grounding switches can be required from the same bay or
from several other bays. When information is needed from other bays, it is exchanged over the
station bus between the distributed IEDs. The problem that arises, even at a high speed of
communication, is a space of time during which the information about the position of the
switching devices are uncertain. The interlocking function uses this information for evaluation,
which means that also the interlocking conditions are uncertain.
294
1MRK 511 358-UUS A
M16602-3 v5
M16609-3 v4
Application manual