ABB Relion 670 Series Applications Manual page 382

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 13
Control
Table 37:
VALID
0
1
1
1
1
13.8.3
Setting guidelines
The function does not have any parameters available in the local HMI or PCM600.
13.9
Single point generic control 8 signals SPC8GAPC
13.9.1
Identification
Function description
Single point generic control 8 signals
13.9.2
Application
The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single
point commands, designed to bring in commands from REMOTE (SCADA) to those parts of the
logic configuration that do not need complicated function blocks that have the capability to
receive commands (for example SCSWI). In this way, simple commands can be sent directly to the
IED outputs, without confirmation. Confirmation (status) of the result of the commands is
supposed to be achieved by other means, such as binary inputs and SPGGIO function blocks.
13.9.3
Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GAPC) function are set via the
local HMI or PCM600.
Operation : turning the function operation Enabled / Disabled .
There are two settings for every command output (totally 8):
376
Description of the input-output relationship
OPEN
-
0
1
0
1
PSTO is the universal operator place selector for all control functions. Even if PSTO
can be configured to allow LOCAL or ALL operator positions, the only functional
position usable with the SPC8GAPC function block is REMOTE.
CLOSE
-
0
0
1
1
IEC 61850
IEC 60617
identification
identification
SPC8GAPC
-
1MRK 511 358-UUS A
POSITION
Value
Description
0
Intermediate
0
Intermediate
1
Open
2
Closed
3
Bad State
ANSI/IEEE C37.2
device number
-
Application manual
SEMOD55398-5 v4
SEMOD176448-1 v3
SEMOD176456-2 v3
SEMOD176511-4 v4
SEMOD176518-4 v5