Section 13
Control
tPoleDiscord is the allowed time to have discrepancy between the poles at control of three single-
phase breakers. At discrepancy an output signal is activated to be used for trip or alarm, and
during a command, the control function is reset, and a cause-code is given.
SuppressMidPos when On suppresses the mid-position during the time tIntermediate of the
connected switches.
The parameter
operate, Sel & Op phase, or only at operate, Op phase.
13.3.3.3

Switch (SXCBR/SXSWI)

tStartMove is the supervision time for the apparatus to start moving after a command execution.
When the time has expired, the switch function is reset, and a cause-code is given.
During the
state. When the time has expired, the switch function is reset, and a cause-code is given. The
indication of the mid-position at SCSWI is suppressed during this time period when the position
changes from open to close or vice-versa if the parameter
SCSWI function.
If the parameter
correct end position is reached. If the parameter is set to
remains active until the timer
tOpenPulse is the output pulse length for an open command. If AdaptivePulse is set to Adaptive , it
is the maximum length of the output pulse for an open command. The default length is set to 200
ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
tClosePulse is the output pulse length for a close command. If AdaptivePulse is set to Adaptive , it
is the maximum length of the output pulse for an open command. The default length is set to 200
ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
13.3.3.4

Bay Reserve (QCRSV)

The timer
be done by requesting bay due to for example communication failure.
When the parameter
apparatus (x) in the bay, only the own bay is reserved, that is, the output for reservation request of
other bays (RES_BAYS) will not be activated at selection of apparatus x.
13.3.3.5

Reservation input (RESIN)

With the
in the SA system.
13.4

Interlocking (3)

The main purpose of switchgear interlocking is:
300
InterlockCheck decides if interlock check should be done at both select and
tIntermediate time the position indication is allowed to be in an intermediate (00)
AdaptivePulse is set to Adaptive the command output pulse resets when a new
tOpenPulsetClosePulse has elapsed.
tCancelRes defines the supervision time for canceling the reservation, when this cannot
ParamRequestx ( x =1-8) is set to Only own bay res. individually for each
FutureUse parameter set to Bay future use the function can handle bays not yet installed
SuppressMidPos is set to On in the
Not adaptive the command output pulse
1MRK 511 358-UUS A
M16675-3 v7
M16677-3 v3
M16678-3 v3
IP15572-1 v2
M13530-4 v3
Application manual