The same philosophy can be used for two-pole tripping and autoreclosing.
To prevent closing of a circuit breaker after a trip the function can block the closing.
The two instances of the SMPPTRC (94) function are identical except, for the name of the function
block (SMPPTRC1 and SMPPTRC2). References will therefore only be made to SMPPTRC1 in the
following description, but they also apply to SMPPTRC2.
15.1.2.1
Three-pole tripping
A simple application with three-pole tripping from the logic block utilizes part of the function
block. Connect the inputs from the protection function blocks to the input TRINP_3P. If necessary
(normally the case) use a logic OR block to combine the different function outputs to this input.
Connect the output TRIP to the digital Output/s on the IO board.
This signal can also be used for other purposes internally in the IED. An example could be the
starting of Breaker failure protection. The three outputs TR_A, TR_B, TR_C will always be activated
at every trip and can be utilized on individual trip outputs if single-pole operating devices are
available on the circuit breaker even when a three-pole tripping scheme is selected.
Set the function block to
example,
For special applications such as Lock-out refer to the separate section below. The typical
connection is shown below in figure 193. Signals that are not used are dimmed.
Impedance protection zone 1 TRIP
Impedance protection zone 3 TRIP
Impedance protection zone 2 TRIP
ANSI05000544 V2 EN-US
Figure 193: Tripping logic SMPPTRC (94) is used for a simple three-pole tripping application
15.1.2.2
Single- and/or three-pole tripping
The single-/three-pole tripping will give single-pole tripping for single-phase faults and three-pole
tripping for multi-phase fault. The operating mode is always used together with a single-phase
autoreclosing scheme.
398
Program = 3Ph and set the required length of the trip pulse to for
tTripMin = 150ms .
OR
EF4PTOC TRIP
SMPPTRC (94)
BLOCK
TRIP
BLKLKOUT
TR_A
TRINP_3P
TR_B
TRINP_A
TR_C
TRINP_B
TR1P
TRINP_C
TR2P
PS_A
TR3P
PS_B
CLLKOUT
PS_C
1PTRZ
1PTRGF
P3PTR
SETLKOUT
RSTLKOUT
1MRK 511 358-UUS A
ANSI05000544-2-en.vsd
Application manual
M14828-7 v8
M14828-11 v4