Communication Settings; Testing The Ied Operation; Selecting The Ied Test Mode - ABB ABILITY SSC600 Operation Manual

Smart substation control and protection for electrical systems
Hide thumbs Also See for ABILITY SSC600:
Table of Contents

Advertisement

Commissioning
1.
2.
3.
3.4.2

Communication settings

The local and remote ports use fixed IP addresses, 192.168.0.254 and 192.168.1.254
respectively, and they also also provide DHCP servers to assign an IP address for the
connected computer. The main communication port Ethernet interface has a factory
default IP address 192.168.2.10 when the complete IED is delivered. The service
communication port Ethernet interface has a factory default IP address 192.168.4.10
when the complete IED is delivered.
Different communication ports are available via optional communication modules.
ETHERNET RJ-45 and optical Ethernet LC are the two station communication port
Ethernet communication options. Station communication port Ethernet is intended for
station bus communication. Communication protocols used via Ethernet ports are IEC
61850-8-1 and IEC 61850-9-2 LE.
3.5

Testing the IED operation

The IED has to be in the test mode before the digital outputs and certain output signals of
protection and other functions can be activated.
3.5.1

Selecting the IED test mode

The test mode can be activated by activating the IED test view. The test mode is useful
for simulated testing of functions and outputs without providing current inputs.
24
Set up or get the IP addresses of the IEDs.
Set up the PC for a direct link or connect the PC or workstation to the network.
Configure the IP addresses in the PCM600 project for each IED.
The addresses are used for communication between IEDs and PCM600.
Note: Use the correct ETHERNET connectors in the IED with redundant
communication protocols like PRP. IEDs with PRP support have two Ethernet
connectors and redundant Ethernet ports are marked as LAN A and LAN B.
Note: The redundant communication module has two operation modes:
"Normal" and "PRP". The operation mode can be changed from
communication settings.
Note: For more information, see the communication protocol manuals and the
technical manual.