Configuration Setting - ABB Relion 670 Series Applications Manual

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 13
Control
(WA1)A1
(WA2)B1
(WA7)C
AB_TRAFO
ANSI04000487 V1 EN-US
Figure 135: Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic for input signals concerning bus-coupler are the same as the specific
logic for the line bay (ABC_LINE):
Signal
BC_12_CL
VP_BC_12
EXDU_BC
The logic is identical to the double busbar configuration "Signals from bus-coupler".
13.4.4.3

Configuration setting

If there are no second busbar B and therefore no 289 disconnector, then the interlocking for 289 is
not used. The state for 289, 2189G, BC_12 are set to open by setting the appropriate module inputs
as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
289_OP = 1
289QB2_CL = 0
2189G_OP = 1
2189G_CL = 0
BC_12_CL = 0
VP_BC_12 = 1
If there is no second busbar B at the other side of the transformer and therefore no 489
disconnector, then the state for 489 is set to open by setting the appropriate module inputs as
follows:
489_OP = 1
489_CL = 0
314
Section 1
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BC
AB_TRAFO
A bus-coupler connection exists between busbar WA1 and WA2.
The switch status of BC_12 is valid.
No transmission error from bus-coupler bay (BC).
Section 2
A2
B2
C
ABC_BC
en04000487_ansi.vsd
1MRK 511 358-UUS A
M13566-22 v5
Application manual