ABB Relion 670 Series Applications Manual page 477

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 358-UUS A
Function blocks with user defined input signals in monitor direction, I103UserDef. These function
blocks include the FUNCTION TYPE parameter for each block in the private range, and the
INFORMATION NUMBER parameter for each input signal.
Supervision indications in monitor direction
Function block with defined functions for supervision indications in monitor direction, I103Superv.
This block includes the FUNCTION TYPE parameter, and the INFORMATION NUMBER parameter is
defined for each output signal.
Ground fault indications in monitor direction
Function block with defined functions for ground fault indications in monitor direction, I103EF.
This block includes the FUNCTION TYPE parameter, and the INFORMATION NUMBER parameter is
defined for each output signal.
Fault indications in monitor direction
Function block with defined functions for fault indications in monitor direction, I103FLTPROT. This
block includes the FUNCTION TYPE parameter, and the INFORMATION NUMBER parameter is
defined for each input signal.
This block is suitable for distance protection, line differential, transformer differential, over-
current and ground-fault protection functions.
Autorecloser indications in monitor direction
Function block with defined functions for autorecloser indications in monitor direction, I103AR.
This block includes the FUNCTION TYPE parameter, and the INFORMATION NUMBER parameter is
defined for each output signal.
Measurands
The measurands can be included as type 3.1, 3.2, 3.3, 3.4 and type 9 according to the standard.
Measurands in public range
Function block that reports all valid measuring types depending on connected signals, I103Meas.
Measurands in private range
Function blocks with user defined input measurands in monitor direction, I103MeasUsr. These
function blocks include the FUNCTION TYPE parameter for each block in the private range, and the
INFORMATION NUMBER parameter for each block.
Fault location
The fault location is expressed in reactive ohms. In relation to the line length in reactive ohms, it
gives the distance to the fault in percent. The data is available and reported when the fault locator
function is included in the IED.
Disturbance recordings
The transfer functionality is based on the Disturbance recorder function. The analog and
binary signals recorded will be reported to the master by polling. The eight last disturbances
Application manual
Section 18
Station communication
M17109-99 v2