ABB Relion 670 Series Applications Manual page 444

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 16
Monitoring
TrigDRN : Disturbance report may trig for binary input N ( Enabled ) or not ( Disabled ).
TrigLevelN : Trig on positive ( Trig on 1 ) or negative ( Trig on 0 ) slope for binary input N.
Func103N : Function type number (0-255) for binary input N according to IEC-60870-5-103, that is,
128: Distance protection, 160: overcurrent protection, 176: transformer differential protection and
192: line differential protection.
Info103N : Information number (0-255) for binary input N according to IEC-60870-5-103, that is,
69-71: Trip L1-L3, 78-83: Zone 1-6.
See also description in the chapter IEC 60870-5-103.
16.6.3.3
Analog input signals
Up to 40 analog signals can be selected among internal analog and analog input signals. PCM600
is used to configure the signals.
The analog trigger of Disturbance report is not affected if analog input M is to be included in the
disturbance recording or not (
OperationM = Disabled , no waveform (samples) will be recorded and reported in graph.
If
However, Trip value, pre-fault and fault value will be recorded and reported. The input channel can
still be used to trig the disturbance recorder.
OperationM = Enabled , waveform (samples) will also be recorded and reported in graph.
If
NomValueM : Nominal value for input M.
OverTrigOpM , UnderTrigOpM : Over or Under trig operation, Disturbance report may trig for
high/low level of analog input M (
OverTrigLeM , UnderTrigLeM : Over or under trig level, Trig high/low level relative nominal value for
analog input M in percent of nominal value.
16.6.3.4
Sub-function parameters
All functions are in operation as long as Disturbance report is in operation.
Indications
IndicationMaN : Indication mask for binary input N. If set ( Show ), a status change of that particular
input, will be fetched and shown in the disturbance summary on local HMI. If not set (
change will not be indicated.
SetLEDN : Set red LED on local HMI in front of the IED if binary input N changes status.
Disturbance recorder
OperationM : Analog channel M is to be recorded by the disturbance recorder ( Enabled ) or not
Disabled ).
(
438
For retrieving remote data from LDCM module, the Disturbance report function
should not be connected to a 3 ms SMAI function block if this is the only intended
use for the remote data.
OperationM = Enabled / Disabled ).
Enabled ) or not ( Disabled ).
1MRK 511 358-UUS A
M12179-92 v4
M12179-389 v3
M12179-448 v4
Hide ), status
M12179-446 v4
Application manual