ABB Relion 670 Series Applications Manual page 296

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 13
Control
IED
Apparatus
Control
CLOSE/OPEN
ANSI08000227 V1 EN-US
Figure 117: Overview of the apparatus control functions
Features in the apparatus control function:
Operation of primary apparatuses
Select-Execute principle to give high security
Selection and reservation function to prevent simultaneous operation
Selection and supervision of operator place
Command supervision
Block/deblock of operation
Block/deblock of updating of position indications
Substitution of position indications
Overriding of interlocking functions
Overriding of synchronism check
Pole discrepancy supervision
Operation counter
Suppression of mid position
The apparatus control function is realized by means of a number of function blocks designated:
Switch controller SCSWI
Circuit breaker SXCBR
Circuit switch SXSWI
Bay control QCBAY
Position evaluation POS_EVAL
Bay reserve QCRSV
Reservation input RESIN
Local remote LOCREM
Local remote control LOCREMCTRL
The signal flow between the function blocks is shown in Figure 118. To realize the reservation
function, the function blocks Reservation input (RESIN) and Bay reserve (QCRSV) also are included
in the apparatus control function. The application description for all these functions can be found
below. The function SCILO in the Figure below is the logical node for interlocking.
290
Station HMI
Local
Local
HMI
HMI
IED
Apparatus
Control
CLOSE/OPEN
breakers disconnectors grounding switches
cc
GW
Station bus
Local
HMI
IED
Apparatus
Control
CLOSE/OPEN
ANSI08000227.vsd
1MRK 511 358-UUS A
Application manual