Section 21
Basic IED functions
ProductDef
FirmwareVer
ProductVer
IEDMainFunType
SerialNo
OrderingNo
ProductionDate
21.3
Measured value expander block RANGE_XP
21.3.1
Identification
Function description
Measured value expander block
21.3.2
Application
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and VNMMXU),
current and voltage sequence measurement functions (CMSQI and VMSQI) and IEC 61850 generic
communication I/O functions (MVGAPC) are provided with measurement supervision
functionality. All measured values can be supervised with four settable limits, that is low-low limit,
low limit, high limit and high-high limit. The measure value expander block ( RANGE_XP) has been
introduced to be able to translate the integer output signal from the measuring functions to 5
binary signals, that is below low-low limit, below low limit, normal, above high-high limit or above
high limit. The output signals can be used as conditions in the configurable logic.
488
Describes the type of the IED. Example:
Describes the release number from the production. Example:
Describes the firmware version.
The firmware version can be checked from Main menu/Diagnostics/IED status/Product
identifiers
Firmware version numbers run independently from the release production numbers. For
every release number there can be one or more firmware versions depending on the
small issues corrected in between releases.
Describes the product version. Example:
1
is the Major version of the manufactured product this means, new platform of the product
2 is the Minor version of the manufactured product this means, new functions or new hardware
added to the product
3 is the Major revision of the manufactured product this means, functions or hardware is either
changed or enhanced in the product
Main function type code according to IEC 60870-5-103. Example: 128 (meaning line
protection).
REL670
2.1.0
IEC 61850
IEC 60617
identification
identification
RANGE_XP
-
1MRK 511 358-UUS A
2.1.0
ANSI/IEEE C37.2
device number
-
Application manual
SEMOD52451-1 v2
SEMOD113212-2 v3
SEMOD52434-4 v5