Figure 161: Switchyard layout double circuit breaker
Three types of interlocking modules per double circuit breaker bay are defined. DB_BUS_A (3)
handles the circuit breaker QA1 that is connected to busbar WA1 and the disconnectors and
grounding switches of this section. DB_BUS_B (3) handles the circuit breaker QA2 that is
connected to busbar WA2 and the disconnectors and grounding switches of this section.
For a double circuit-breaker bay, the modules DB_BUS_A, DB_LINE and DB_BUS_B must be used.
13.4.8.2

Configuration setting

For application without 989 and 989G, just set the appropriate inputs to open state and disregard
the outputs. In the functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
989_OP = 1
989_CL = 0
989G_OP = 1
989G_CL = 0
If, in this case, line voltage supervision is added, then rather than setting 989 to open state,
specify the state of the voltage supervision:
989_OP = VOLT_OFF
989_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
VOLT_OFF = 1
VOLT_ON = 0
Application manual
189
189G
152
289G
6189
989
989G
WA1 (A)
WA2 (B)
289
489G
DB_BUS_B
252
589G
6289
389G
DB_LINE
en04000518_ansi.vsd
Section 13
Control
M13584-4 v4