Enabled LED is not illuminated solid green, check to see that closed contacts or
jumpers connect terminal X2:3 to X2:4 and X2:2 to X2:7 on the bypass control
board.
5. On the E-Clipse Bypass control panel, either the Drive Selected or Bypass Selected
LED should be illuminated. Pressing the Drive Select or Bypass Select key should
switch the bypass back and forth between the Drive mode and the Bypass mode as
indicated by the LEDs above each button. Check that the bypass control panel
switches the system between modes. Leave the system in the Bypass mode when
proceeding to the next step.
6. Check to see that pressing the:
• Auto key on the bypass control panel causes the bottom line on the E-Clipse
Bypass display to indicate "Bypass in Auto".
• Hand key on the bypass control panel generates a Motor Phase Fault.
• Under normal conditions (motor connected) pressing the Hand key on the bypass
control panel causes the bottom line on the E-Clipse Bypass display to indicate
"Hand #A Run".
• OFF key on the bypass control panel causes the bottom line on the E-Clipse
Bypass display to indicate "Off Stop".
7. For Steps 8 through 14, ACH580 Drive Parameter 99.04 must be set to "Scalar".
After successful completion of Step 13, Parameter 99.04 may be set to "Vector" if
very specific application requirements make it necessary to use this type of motor
control. Operation using the "Vector" setting is unnecessary for control of almost all
fan and pump applications. Refer to the ACH580 firmware manual
(3AXD50000027537) for details on setting parameters.
8. Press the Drive Select key on the E-Clipse Bypass control panel. The Drive Select
LED should be illuminated.
9. Check to see that pressing the:
• Auto key on the bypass control panel causes the E-Clipse Bypass display to
indicate "Bypass in Auto".
• Hand key on the bypass control panel causes no change to the E-Clipse Bypass
display.
• OFF key on the bypass control panel causes the E-Clipse Bypass display to
indicate "Bypass in Off".
10. Press the HAND key on the drive control panel. Note that the top line of the control
panel display indicates "HAND" and run as a clockwise rotating arrow. The Drive
Run LED on the E-Clipse Bypass control panel should be illuminated.
11. Press the UP arrow on the drive control panel. Note that the speed reference
indication in the top line of the drive control panel display increases from "0 HZ".
12. In the middle line of the drive control panel display, the output current indication
should indicate "0.0 A."
13. Press the DOWN arrow on the drive control panel until the speed and frequency
indications return to "0.0."