Technical Data - ABB ACH580 Series User Manual

E-clipse bypass and packaged drive
Table of Contents

Advertisement

ACH580 E-Clipse bypass and packaged drive user manual

Technical data

Power connection terminals
The following tables show maximum wire size and required tightening torque for
incoming power, grounding and motor terminals.
Output
208/230 Volt
Ratings
1
Type Code
A
ACH580-PxR-04A6-2
4.6
ACH580-PxR-06A6-2
6.6
ACH580-PxR-07A5-2
7.5
ACH580-PxR-10A6-2
10.6
ACH580-PxR-017A-2
16.7
ACH580-PxR-024A-2
24.2
ACH580-PxR-031A-2
30.8
ACH580-PxR-046A-2
46.2
ACH580-PxR-059A-2
59.4
ACH580-PxR-075A-2
74.8
ACH580-PxR-088A-2
88
ACH580-PxR-114A-2
114
ACH580-PxR-143A-2
143
ACH580-PxR-169A-2
169
ACH580-PxR-211A-2
211
ACH580-PxR-248A-2
248
1) "PxR" represents both PCR and PDR.
2) 100 HP @ 230V.
Base
Circuit
Drive
Breaker
Frame
UL
HP
Size
(NEMA)
UL (NEMA)
Type 1
and 12
1
R1
1.5
R1
#10
62 in-lbs
2
R1
3
R1
5
R1
#6
62 in-lbs
7.5
R2
#4
10
R2
62 in-lbs
#2
15
R3
62 in-lbs
#1
20
R3
62 in-lbs
#1/0
25
R4
62 in-lbs
#2/0
30
R5
124 in-lbs
#1/0
40
R5
124 in-lbs
#3/0
50
R6
124 in-lbs
#4/0
60
R7
124 in-lbs
2 X 500
75
R7
MCM
274 in-lbs
373
2
100
R8
MCM
274 in-lbs
Maximum Power Wiring Data
Disconnect
Circuit
Disconnect
Switch
Breaker
Switch
UL (NEMA)
UL (NEMA)
Type 1
Type 3R
Type 3R
and 12
#10
#10
62 in-lbs
55 in-lbs
55 in-lbs
#6
#6
62 in-lbs
55 in-lbs
55 in-lbs
#4
#4
62 in-lbs
55 in-lbs
55 in-lbs
#2
#2
62 in-lbs
55 in-lbs
55 in-lbs
#1
#1
62 in-lbs
55 in-lbs
55 in-lbs
#1/0
#1/0
#1/0
62 in-lbs
55 in-lbs
55 in-lbs
#2/0
275 in-lbs
#4/0
275 in-lbs
200 MCM
Consult
275 in-lbs
Consult
Factory
Factory
2 X 500
MCM
274 in-lbs
Ground
Lugs
Motor
UL
Terminals
(NEMA)
Type 1
and 12
#10
#10
0.7 ft-lbs
#6
#2
#6
50 in-lbs
#4
1.1 ft-lbs
#2
#2
2.6 ft-lbs
#1
#1
3.0 ft-lbs
#2/0
4.1 ft-lbs
300 MCM
22.1 ft-lbs
#1/0
50 in-lbs
500 MCM
29.5 ft-lbs
2 x 300
MCM
29.6 ft-lbs
Technical data
237
Ground
Lugs
UL
(NEMA)
Type 3R
#2
50 in-lbs
Consult
Factory

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents