ACH580 E-Clipse bypass and packaged drive user manual
Actual value
As described earlier in
values.
Actual value scaling
The scaling of the integers sent to the fieldbus as Actual Values depends on the
resolution of the selected drive parameter. Except as noted for Data Words 5 and 6
below, scale the feedback integer using the resolution listed for the parameter in the
ACH580 HVAC control program firmware manual (3AXD50000027537). For
example:
100 (example: 12.11 AI1 actual
feedback)
10
Data words 5 and 6 are scaled as follows:
Data Word
5
6
Actual value mapping
See the user's manual supplied with the FBA module.
Control
Feedback Integer
Contents
Set by drive
-20000 ... +20000 = -(par 46.01) ... +(par 46.01) if content is Speed
parameter
-20000 ... +20000 = -(par 46.02) ... +(par 46.02) if content is Frequency
58.28
-10000 ... +10000 = -(par 46.03) ... +(par 46.03) if content is Torque
Set by drive
-20000 ... +20000 = -(par 46.01) ... +(par 46.01) if content is Speed
parameter
-20000 ... +20000 = -(par 46.02) ... +(par 46.02) if content is Frequency
58.29
-10000 ... +10000 = -(par 46.03) ... +(par 46.03) if content is Torque
interface, Actual Values are words containing drive
Scaling
(Feedback Integer) / (Scaling) = Scaled Value
1000 = 1 unit
100 / 1000 = 0.1 mA
10 = 1%
10 / 10 = 1%
ABB Drives Profile
Scaling
Fieldbus adapter
181