ABB ACH580 Series User Manual page 198

E-clipse bypass and packaged drive
Table of Contents

Advertisement

ACH580 E-Clipse bypass and packaged drive user manual
Fault
Code
3023
3024
3027
3028
3029
3030
3031
...
3033
3034
3037
Fault Name
Fault
In Panel
BYP COIL
Coil characteristics are
SHORTED
checked only on power
up and coil current is
greater than allowable
values
DRV COIL
Coil characteristics are
SHORTED
checked only on power
up and coil current is
greater than allowable
values
INVALID SUB
Contactor assembly as
ASM
recorded in the RBCU
unit does not match
drive information
communicated via 485
link
EXT COMM
Time between fieldbus
LOSS
messages has
exceeded timeout
interval set with
parameter 3005
EFB CONFIG
Error reading
FILE
configuration file for
embedded fieldbus
FORCE TRIP Fault trip forced by
external fieldbus
EFB 1...EFB 3 Fault code reserved for
embedded fieldbus.
MTR PHASE Detects open motor
phase. Detection is
done by current
transformers in bypass
unit.
PCB TEMP
RBCU unit has reached
190 degrees Fahrenheit,
88 degrees Celsius
Possible Cause
Shorted contactor
Replace RBCU
coil
Replace RCSA unit
Shorted/damaged
cable
Bad RBCU
Shorted contactor
Replace RBCU
coil
Replace RCSA unit
Shorted/damaged
cable
Bad RBCU
RBCU unit from a
Contact ABB at
different size bypass
1-800-752-0696 option 1
used to replace a
defective RBCU.
Parameters not
matched after
Firmware change.
Incorrect
Check Group 51 and 58
Communication
Tighten Connections
settings in Group 51
Check Communication Cable
and 58.
Grounding
Poor Connections
Noise on
Communication Line
Internal Startup error Cycle Power
Replace RBCU
Overriding Control
Check Overriding Control
System tripped
System
E-Clipse unit via
fieldbus.
For Bacnet: Device
Check Parameters 5040,
object instances for
5099 and/or 5840, 5899
the drive and or
bypass are set
greater than
4194302 in
parameters 5040
5099 and/or 5840
5899 respectively
Internal problem
Check wiring in E-Clipse Unit
Cable problem
Check motor cabling
Motor problem
Check Motor
Check if 3006 is Disabled
Cabinet cooling has
Stop drive and let cool down
failed
and restart
Ambient conditions
Add additional cooling
too high
Replace RBCU
Bad RBCU unit
189
Corrective Action
Diagnostics