ABB ACH580 Series User Manual page 73

E-clipse bypass and packaged drive
Table of Contents

Advertisement

64
Code
1411
1412
1413
1414
1415
Group 16: System Control
Code
1601
1602
1603
1604
1605
1606
1607
1608
1609
1610
1611
1612
1613
1614
1615
Parameters
Name
Resolution
R4 ON DLY
0.1 sec
R4 OFF DLY
0.1 sec
RO5 SELECT
1
R5 ON DLY
0.1 sec
R5 OFF DLY
0.1 sec
Name
Resolution
START/STOP
1
PERMISSIVE
1
INTERLOCK 1
1
INTERLOCK 2
1
INTERLOCK 3
1
INTERLOCK 4
1
RESET SRC
1
AUTO XFR
1
OC TRANSFR
1
OV TRANSFR
1
UV TRANSFR
1
AI TRANSFR
1
BP DISABLE
1
BP RUN DLY
1 sec
SAVE PARAM
1
ACH580 E-Clipse bypass and packaged drive user manual
Group 14: Relay Outputs
Range
0-3600.0s
0-3600.0s
See RO 1 Select.
0-3600.0s
0-3600.0s
Group 16: System Control
Range
Default
0 = NOT SEL
1 = DI1
2 = COMM
0 = NOT SEL
NOT SEL
1 = DI2
2 = COMM
0 = NOT SEL
1 = DI3
2 = COMM
0 = NOT SEL
NOT SEL
1 = DI4
2 = COMM
0 = NOT SEL
NOT SEL
1 = DI5
2 = COMM
0 = NOT SEL
NOT SEL
1 = DI2
2 = COMM
0 = NOT SEL
NOT SEL
1 = DI4
2 = COMM
0 = NOT SEL
NOT SEL
1 = ENABLE
0 = NOT SEL
NOT SEL
1 = ENABLE
0 = NOT SEL
NOT SEL
1 = ENABLE
0 = NOT SEL
NOT SEL
1 = ENABLE
0 = NOT SEL
NOT SEL
1 = ENABLE
0 = NOT SEL
NOT SEL
1 = DISABLE
0 - 300 secs
0 = DONE
1 = SAVE
Default
Description
0s
Delay from active state to
active output.
0s
Delay from inactive state
to inactive output.
BYPASS
AUTO
(13)
0s
Delay from active state to
active output.
0s
Delay from inactive state
to inactive output.
Description
DI 1
Selects source for system start
(1)
command.
Selects source for the
(0)
permissive command.
DI 3
Selects source for the interlock 1
(1)
command.
Selects source for the interlock 2
(0)
command.
Selects source for the interlock 3
(0)
command.
Selects source for the interlock 4
(0)
command.
Selects source for fault reset
(0)
command (rising edge).
Enabled allows auto transfer to
(0)
bypass on all drive faults except
the conditional faults which
require an additional enable.
NOT SEL prevents auto transfer
to bypass for all drive faults
including the conditional faults.
Drive over current causes auto
(0)
transfer. Requires global auto
transfer enable also.
Drive over voltage causes auto
(0)
transfer. Requires global auto
transfer enable also.
Drive under voltage causes auto
(0)
transfer. Requires global auto
transfer enable also.
Drive AI loss causes auto
(0)
transfer. Requires global auto
transfer enable also.
Disables bypass mode.
(0)
0s
Bypass contactor pick-up delay
when starting bypass or
transferring from Drive mode.
0
Save User Settings (SaveImm +
SavePwrd).

Hide quick links:

Advertisement

Table of Contents
loading