ABB ACH580 Series User Manual page 96

E-clipse bypass and packaged drive
Table of Contents

Advertisement

ACH580 E-Clipse bypass and packaged drive user manual
Drive relay output control
Using the fieldbus for relay output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Drive Parameter
10.24 RO1
RELAY
Source
OUTPUT 1
10.27
RELAY
OUTPUT 2
10.30
RELAY
OUTPUT 3
1)
15.07
RELAY
OUTPUT 4
1)
15.10
RELAY
OUTPUT 5
1
15.23
DIGITAL
DO1 Source
OUTPUT 1
1) More than 3 relays requires the addition of a relay extension module.
For example: To control relays 1 and 2 using serial communication:
Set parameters 10.24
Then, for example using N2:
• To turn Relay 1 On: Force object BO7 to On.
• To turn Relay 2 On: Force object BO8 to On.
• To turn both Relay 1 and 2 On: Force objects BO7 and BO8 On.
Note: Relay status feedback occurs without configuration as defined below.
Drive Parameter
10.21 RO Status
RO 1-3 STATUS
RO 4-5 STATUS
15.04 RO/DO
Status
DOI STATUS
Analog output control
Using the fieldbus for analog output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Value
Setting
62, RO/DIO
Relay Output 1 controlled
control word
by fieldbus.
62, RO/DIO
Relay Output 2 controlled
control word
by fieldbus.
62, RO/DIO
Relay Output 3 controlled
control word
by fieldbus.
62, RO/DIO
Relay Output 4 controlled
control word
by fieldbus.
62, RO/DIO
Relay Output 5 controlled
control word
by fieldbus.
62, RO/DIO
Digital Output 1 controlled
control word
by fieldbus.
1 Source = 62, RO/DIO control word.
RO
Value
Relay 1...3 status.
Relay 4...6 status.
Modbus
ABB DRV
402659 bit 0 or 00033
402659 bit 1 or 00034
402659 bit 2 or 00035
402659 bit 3 or 00036
402659 bit 4 or 00037
402659 bit 8 or 00038
Protocol Reference
Modbus
Setting
ABB DRV
PROFILE
N/A
402581 or 00033...35
N/A
403844 or 00036...37
N/A
403844 or 00038
Protocol Reference
N2
BACnet
DCU
PROFILE
BO7
BO0
BO8
BO1
BO9
BO2
BO10
BO3
BO11
BO4
BO12
BO5
N2
BACnet
DCU
BI4...BI6
BI0...BI2
BI7...BI8
BI3...BI4
BI9
BI5
Embedded fieldbus
87