E-Clipse Bypass control unit connections (RBCU)

Control cable requirements for connections to the E-Clipse Bypass (RBCU) (X2) are the
same as those described for the ACH580 control panel (X1). Refer to the ACH580-01
Hardware Manual (3AXD50000044839) for additional information.
Bypass control unit connection specifications
Digital Inputs
Relays
(Digital Outputs)
WARNING! Relay coils generate noise spikes
in response to steps in applied power. To avoid
drive damage from such spikes, all AC relay
coils mounted across control panel inputs
require R-C snubbers, and all DC relay coils
mounted across control panel outputs require
diodes – see figure.
Bypass control unit terminals
The following table provides specifications for the E-Clipse Bypass's control unit
terminals.
Frame Size
Technical data
Control Connection Specifications
Digital input impedance 1.5 k. Maximum voltage for digital inputs is 30 V AC/DC
• Max. contact voltage: 30 V DC, 250 V AC
• Max. contact current / power: 6 A, 30 V DC; 1500 VA, 250 V AC
• Max. continuous current: 2 A rms (cos . = 1), 1 A rms (cos. = 0.4)
• Minimum load: 500 mW (12 V, 10 mA)
• Contact material: Silver-nickel (AgN)
• Isolation between relay digital outputs, test voltage: 2.5 kV rms, 1 minute
Maximum Wire Size
2
mm
All
0.12...2.5
ACH580 E-Clipse bypass and packaged drive user manual
Control
Torque
AWG
N•m
26...14
0.4
0.47 uF
AC Coil
33 Ohm
Typical R-C
Snubber
+
DC Coil
Diode
-
lb-ft
0.3
Control
Panel
Inputs
Control
Panel
Outputs