Activate drive control functions – FBA
Fieldbus control of various drive functions requires configuration to:
• Tell the drive (via the bypass) to accept fieldbus control of the function.
• Define as a fieldbus input, any drive data required for control.
• Define as a fieldbus output, any control data required by the drive.
The following sections describe, at a general level, the configuration required for
each control function. The last column in each table below is deliberately blank. See
the user's manual supplied with the FBA module for the appropriate entry.
Start/stop control
Using the fieldbus for start/stop/direction control of the drive only requires:
• Bypass parameter values set as defined below.
• Fieldbus controller supplied command(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Bypass Parameter
1601 START/STOP
1625 COMM CTRL
Input reference select
Using the fieldbus to provide input reference to the drive requires:
• Drive parameter value set as defined below.
• Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Ext1/Ext2 Select
Ext1
Ext2
Fieldbus adapter
ACH580 E-Clipse bypass and packaged drive user manual
Value
2 (COMM)
Selects Source for system
start command.
0 (DRIVE
Enable drive only control.
ONLY)
Scalar Control
(Group 28)
Ref1
28.11
Ref2
28.12
Ref1
28.15
Ref2
28.16
Description
ABB DRV
400001 bits
0...3
N/A
Vector Control
(Group 22)
19.11
22.11
22.12
22.15
22.16
Protocol Reference
1
Modbus TCP
DCU
PROFILE
40031 bits 0, 1
Value
2 FBA MCW bit 11
Flexibility to write to 3.04
(FB A ref1) or 3.05 (FB A
ref 2)