ACH580 E-Clipse bypass and packaged drive user manual
Activate drive control functions
Controlling the drive
Fieldbus control of various drive functions requires configuration to:
• Tell the drive to accept fieldbus control of the function.
• Define as a fieldbus input, any system data required for control (drive only or
system)
• Define as a fieldbus output, any control data required by the drive.
The following sections describe the configuration required for each control function.
Note: The user should change only the parameters for the functions you wish to
control via BACnet. All other parameters should typically remain at factory default.
Start/stop direction control – Drive
Using the fieldbus for start/stop/direction control of the drive requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied command(s) in the appropriate location.
Bypass Parameter
1601 START/STOP
1625 COMM CTRL
1) Ext1 = Ref 1
Ext 2 = Ref 2; Ref 2 normally used for PID setpoint commands.
Input reference select
Using the fieldbus for start/stop/direction control of the drive requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied command(s) in the appropriate location.)
Ext1/Ext2 Select
Ext1
Ext2
Value
2 (COMM)
Start/Stop by fieldbus with Ext1 or Ext2
selected
0 (Drive
1625 = 0 for control signals (Start/Stop and
Only)
enables) to go to drive only
1 (System)
1625 = 1 for control signals to go to the
system (drive or bypass, depending on
keypad mode selection)
Scalar Control
(Group 28)
Ref1
28.11
Ref2
28.12
Ref1
28.15
Ref2
28.16
Description
Vector Control
(Group 22)
19.11
22.11
Flexibility to write to 3.09
22.12
(EFBRef1) or 3.10
22.15
(EFBRef2)
22.16
117
BACnet
Access Point
1
BV10
N/A
Value
32, EFB MCW bit 11
Embedded fieldbus